Blog #8 - Residential Electrical Power Chapter Three

Residential Electrical Power Chapter Three

Low Voltage Circuit Protection

American wire gauge (AWG), also known as the Brown & Sharpe wire gauge, is a logarithmic stepped standardized wire gauge system used since 1857, predominantly in North America, for the diameters of round, solid, nonferrous, electrically conducting wire. The cross-sectional area of each gauge is an important factor for determining its current-carrying ampacity.

Low Voltage wiring will involve the requirement of different sizes or gauges of wire depending on the load that it feeds or more precisely, the amperage it will have to carry. Wire sizes are categorized by what is standard in North America as the American Wire Gauge. This is a measure of wire thickness (which also dictates cross-sectional area, and for a given material, ampacity). For example…24 AWG wire has a nominal diameter of 0.0201in or 0.511mm. AWG only applies to wire used to conduct electricity.

These above two charts describe the characteristics and capabilities of the various wire gauges of copper wire.The chart with the white background is the current caring capacity of the various copper conductors…for example for a load that draws 15 amps #14 AWG wire is required. The chart with the green background, along with describing the diameter indicates the resistance of the wire in ohms per foot. This is only significant for long runs of cables.

 

Due to the current carrying capacity of the various gauges of wire sizes, the figure on the left shows the breaker rating and type, single pole single throw (SPST) and single pole double throw (SPDT), required for the various wire gauges.

Circuit protection is employed to protect wires and electrical equipment from damage in the event of an electrical overload, short circuit, or ground fault. Lightning storms, overloaded power outlets, or a sudden electrical surge may result in a dangerous situation with the potential to cause fire, equipment damage, or personal injury. Circuit protection is designed to eliminate this risk before it occurs by cutting off the power to the circuit.

A circuit breaker is a protection device employed in every electrical circuit to prevent any potential hazard. There are different types of circuit breakers used all over the world due to their various characteristics & applications. It is necessary to have a circuit breaker that offers adequate protection so that one can work safely around it without having fear of any potential hazards. That is why it is best to know about these kinds of circuit breakers & what kinds of protection do they offer before buying one.

 
 

A circuit breaker breaks the circuit in case of overloading & short circuit. The fault currents generated due to these fault conditions can damage the electrical devices as well as cause fire in a building that can also pose danger to human life. The circuit breaker instantly cut off the power supply to reduce further damage.

A circuit breaker has two types of tripping units i.e. a thermal unit and a magnetic tripping unit.

The thermal tripping unit is used for protection against overloading. It uses a bi-metallic contact that bends with a change in temperature. The current flowing through the bimetallic strip heats up contact & trips the circuit breaker. The rate of bending of the bi-metallic strip depends on the amount of current. Therefore, the greater the overloading current, the faster the circuit breaker trips.

The magnetic trip unit is used for protection against short circuit current. It includes a solenoid that produced a strong magnetic field due to a high short circuit current to instantly trip the circuit breaker.

The expected behaviour of a circuit breaker depends on its design and what it is designed for. This behaviour is best described by a Trip Curve.

A trip curve is a graphical representation of the expected behaviour of a circuit breaker. Trip curves plot the interrupting time of circuit breakers based on a given current level. They are provided by the manufacturers of circuit breakers to assist users with selecting breakers that provide proper equipment protection and performance while avoiding nuisance tripping.

To avoid nuisance trips, circuit breakers need to be sized appropriately to compensate for inrush current. NEMA defines instantaneous peak inrush as the momentary current transient that occurs within half an AC cycle after contact closure.

Inrush current is what causes lights to dim in a house when a motor, such as that on a clothes dryer or vacuum cleaner starts up.

We need different trip curves in order to balance the right amount of overcurrent protection against optimal machine operation. Choosing a circuit breaker with a trip curve that trips too soon can result in nuisance tripping. Choosing a circuit breaker that trips too late can result in catastrophic damage to machine and cables.

The three most common trip curves for Miniature Circuit Breakers are B, C and D. By putting all three on one chart, we can see how the thermal portion of the curves are similar to each other, but there are differences in how the magnetic curve, and thus the circuit breaker functions.

The tripping curve tells how fast a circuit breaker will trip at a specific current. The different tripping curves classify the circuit breakers into categories where each category is used for specific types of loads. It is essential to select a circuit breaker that provides the necessary overcurrent protection.

Type B circuit breakers are designed to instantly trip when the operating current is 3 to 5 times its rated current. Their tripping time falls between 0.04 to 13 seconds. They are suitable for domestic applications where surges are very low such as lighting, small motors & resistive loads.

Type C circuit breakers trip instantly at current surges 5 to 10 times its rated current. Its tripping time lies between 0.04 to 5 seconds. As they can tolerate higher surge currents, they are used in commercial applications such as the protection of small motors, transformers, etc.

Type D circuit breakers trip instantly when operating currents reach 10 to 20 times their rated current. Its tripping time is 0.04 to 3 seconds. Such circuit breakers can tolerate the high inrush current of large motors. Therefore, they are suitable for running heavy loads in industrial applications.

According to NEC (National Electric Code), IEC (International Electrotechnical Commission) and IEEE (Institute of Electrical and Electronics Engineers), a proper size a circuit breaker is a must for all electrical circuits i.e. residential wiring and industrial or commercial installation to prevent the electrocution, hazardous fire and protection of the connected electrical equipment and appliances.

For maximum safety and reliable operation of the electrical machines, it is recommended to use the correct and suitable size of the circuit breaker according to the circuit’s current flowing through it. If we don’t use a correctly sized circuit breaker. In case of other (over or lower) sizes instead of the correct-sized circuit breaker, the circuit, cables and wire even the connected device may heat up or in case of a short circuit, it may start to smoke and burn. That’s why a correct size circuit breaker is needed for smooth operation.

Under normal conditions when the circuit current rating is lower than 80% of the circuit breaker rating, the circuit operation is normal and the circuit breaker will not trip. In case of fault or short circuit when the value of current exceeds the circuit breaker rating, It will automatically trip i.e. break the circuit from the supply.

For example, a 30 amp circuit breaker will trip at or above 30 amp no matter if is it a continuous or noncontinuous load. However, just after the current exceeds 80%, of the circuit breaker rating, even buy a small amount, the thermal element of the breaker will start to heat up and if the current does not drop below 80%, but continues to flow the breaker will eventually trip after a long period of time.

That’s why we must select 20-25% higher for circuit breaker rating than the expected, flowing current in the cables and wires to the connected device.

In order to determine the appropriate size of circuit breaker for single phase supply, it depends on multiple factors, like the type of load, cable material and even the environment temperature.

The general rule of thumb is that circuit breaker size should be 125% of the ampacity of cable and wire or the circuit which has to be protected by the circuit breaker. Let see the following solved examples:

Example# 1

Suppose, a 12 gauge wire is used for 20 amperes lighting circuit having 120V single phase supply. What is the best size of circuit breaker for that 20 A circuit?

Solution:

Circuit Current: 12A

Circuit Breaker size should be 125% of the circuit current = 125% x 20A

Circuit Breaker Size = 25A

Example #2

What is the appropriate size of circuit breaker for 2000W, single phase 120V Supply?

Solution:

Load: 2000W

Voltage: 120V (Single Phase)

Circuit Current: I = P / V

I = 2000W / 120V

I = 16.66 A.

Circuit Breaker Size: 1.2 or 1.25 to the load current.

1.2 x 16.66 A

Circuit Breaker Size = 20 A.

Circuit protection is employed to protect the wires and electrical equipment from damage in the event of an electrical overload, short circuit, or ground fault. Lightning storms, overloaded power outlets, or a sudden electrical surge may result in a dangerous situation with the potential to cause fires, equipment damage, or personal injury. Circuit protection is designed to eliminate this risk before it occurs by cutting off the power to the circuit. Circuit protection devices include fuses, miniature circuit breakers, molded case circuit breakers, supplementary protectors, motor protection circuit breakers, overload relays, electronic fuses and air circuit breakers.

Trip Curves predict the behavior of circuit protection devices in both slower, smaller overcurrent conditions, and larger, faster overcurrent conditions. Choosing the correct trip curve for your application provides reliable circuit protection while limiting nuisance or false trips.

This blog is a brief overview of circuit breakers. It is not intended to be the final answer on this topic. There is a lot more to learn, including other types of trip curves and circuit breaker coordination. With the basics now covered, one can confidently approach those topics.

Blog #7 - Residential Electrical Power Chapter Two

Residential Electrical Power Chapter Two

This blog is designed to give the reader an introduction to the low-voltage electrical wiring found in residential homes. Most of it applies to any installation that uses a 120/240 AC volt supply. Of course, there are numerous permutations and combinations involved, but this blog will explain the most used and generally, familiar to the public situations. It is designed around the national electric code (NEC) but codes vary depending on where you are in North America and indeed the world. As a disclaimer, I am going to say that some of the wiring and some of the statements may not apply to local electrical codes. In order to be sure, the student should check with the local authorities first, prior to changing any wires wiring in their homes. At the very least this blog will provide a starting point.

This first chapter will cover some of the essential rules that we will follow when justifying some of the circuitry to be found later. The first thing that is to be known, is that all functioning elements form electric circuits and current will flow from positive to negative in a circular fashion around a loop regardless if we are using AC or DC power sources. All electric circuits have Voltage, Current and Resistance that are related by Ohm's Law which states that the current in a circuit will very directly as the voltage and inversely as the resistance in the circuit. In this illustration, current will flow in a circuit formed by the wires connecting the battery through the lightbulb back to the battery. The voltage of the source equals the voltage drop across the lightbulb in this case 120 Volts.

Of course, batteries don't operate household systems. It is AC current that is changing polarities 60 times a second (in North America). The filament in the lightbulb does not get a chance to cool in between the cycle changes, hence the light looks like it's on steady, which indeed it is. The use of AC current is mainly because it allows for voltage transformation. That is, to be stepped up and transferred over long distances and then stepped down to lower levels to make it useful and safe within homes.

Let’s have a closer look at this changing polarity of 60 times a second. If we look at the voltage in the system it starts at “0” rises to a maximum then reduces back to “0” and proceeds to a negative maximum then goes back to “0” again. It repeats itself every 1/60th of a second. It does this in what is called a “sinusoidal” shape, as you see here in blue.For simplicity we will assume that most loads are resistive in nature (lightbulbs, baseboard electric heaters, electric stoves and ovens, etc.) Therefore, the instantaneous current in the circuit will follow the voltage and it too will be “sinusoidal”. We say that it is “in-phase” with the voltage, as you see here in red.The question now becomes…How do we describe the magnitude of this sinusoidal voltage and current, if it is continuously changing?…There are several ways.

We can measure and compare the amplitude or peak…Another way is to measure and compare the peak to peak. Still another way, is to average the curve…but that would just be “0”…not too useful…Unless we squared the value first, then found the square root. This would essentially change the shape of the curve placing all of the curves above zero. Now we could average the value of this voltage or current and it would be a positive value and greater than “0”. This value is known as the “Root-Mean-Square” or RMS value of the voltage and current and it is exactly the square root of 2 or 0.707 times the peak value.

This averaging is the equivalent of shaving off the areas of the peaks of the curve above the RMS line, (the mauve dotted line) which would exactly fill the space between the curves below the RMS line. This may seem like a bit of mathematical manipulation, however as it turns out it is very useful in calculating the average power and energy consumed by a customer. And as a matter of fact, all AC current and voltages are measured in RMS values and all voltmeters, ammeters, and multi-meters, unless otherwise stated are registered in RMS values. If you have a closer look at the average quality of the voltage overtime here it is exactly what the DC voltage would look like and in fact RMS values are often referred to as the DC equivalent of AC voltage and current.

The RMS values of current and voltages are used in calculating the average power and energy consumed. The power draw that a load such as a lightbulb takes from the circuit is expressed in watts. The load in power rating is usually marked on the device such as a lightbulb and in this case, it is 100 Watt bulb. The power in watts consumed by a load is given by the current times the voltage (using RMS values) or W = I x V.

Because the current in a circuit is equal to the voltage divided by the resistance, then we can rewrite the equation for watts in either of the following two ways… as depicted in the graphic above.

As a final note, the standard symbol for an AC generator is not a two-ended battery but a simple circle with a sinusoidal wave shape.

Quite often we have to calculate the current that a specific load will draw given its rating in watts and we know the connected voltage. In that case we will use the first equation re-written. For example, if the load were a 100 Watt incandescent light bulb. and we know that the connected voltage is 120 V. Then the connected current is 100/120 or 0.83 Amps.

Now if the load were not a 100 Watt incandescent light bulb but a 1 kilowatt heater and the connected voltage is still 120 V. Then the connected current is 1000/120 or 8.33 Amps.

Keeping the load of a 1 kilowatt heater and change the connected voltage to 240 V. Then the connected current is 1000/240 or dropping the current to 4.17 Amps. This time the 1 kW heater is rated at 240 V not 120 V.

Looking at the power panel and the incoming connections from the utility.

Measuring the voltages over time…Remember, voltage is a measurement of the potential difference between two points. Let’s measure that voltage over time starting with the potential difference between the hot terminal “A” with respect to the neutral. As you see it rises to a maximum of 120 V positive then returns to zero and goes to -120 V and back to zero and repeats itself. It will do this 60 times a second. Repeating the measurement this time of the hot terminal "B" with respect to the neutral. As you see it rises to a maximum of -120 V and then returns to zero and goes to +120 V and back to zero and repeats itself. It will do this 60 times a second. As is evident from this time measurement, the voltages are, at all times, out of phase with each other. In fact, they are 180° out of phase with each other. That means if we take the measure of the potential difference between the two hot terminals. The potential difference between the two hot terminals “A” & “B” with respect to each other, rises to a maximum of 240 Volts positive then returns to zero and goes to -240 V and back to zero and repeats itself 60 times a second. In this way, the utility can supply both 120 V and 240 V to this customer.

Blog #6 - Residential Electrical Power Chapter one

Residential Electrical Power Chapter one

This blog covers general information about what you will generally find in North American residential electrical power systems. It is focused mainly on theoretical and observational information. It is not a comprehensive guide to regulations or safety requirements. For any “do it yourself work” you are encouraged to consult with your local utility and safety regulations before starting any work.

Connecting homes to the electrical grid is the final stage of the electrical grid. After the distribution grid's substations have stepped-down the voltage to safe levels, this stage may be accomplished. Wires lead off from the neighbourhood's power lines and connect to individual buildings (homes, apartments, businesses,) by first going through the electric meter to measure how much electricity the home uses. The electricity then passes through a service panel, which houses the electrical safety devices (circuit breakers or fuses). This service panel has all of the wires that run to the different electrical appliances around the house.

Every home is connected to the electrical grid through some sort of fuse box or circuit breaker.

The overhead power connection from the utility lines to the service entrance is referred to as the service drop. It has three wires. One neutral line and two hot lines. The hot lines maintain a certain potential (like 120 V) compared to the neutral line. There are two types of overhead service drops, a mast service drop, or an underground service connection.

The service connection enters the panel via the main disconnect breaker, which is utilized during emergencies to stop electrical power flow. This is positioned in between the service meter and the rest of the electrical panel. The main disconnect is a circuit breakers housed in the electrical panel. In order for this to work the circuit breakers must be in series with the two hot lines of the conductors because it must cut power to all circuits. It is rated to be able to interrupt the total household load.

This diagram to the right, illustrates some of the most common circuits found in a typical circuit breaker service panel box. The breakers are installed in a panel so that contact is made with one or both of the hot bus bars running down the middle of the box. The hot wire for a branch circuit is connected to the breaker by a set screw on the base. The neutral and ground wires for the circuit are connected to a bar along the side of the service panel box. The neutral and grounding bars in the panel may be separate or, in the case of older service panels, the same bar may be used for both purposes.

This wiring diagram illustrates installing a 15 amp circuit breaker for a 120 volt branch circuit. The 14/2 awg cable for this circuit includes 2 conductors and 1 ground wire. A 15 amp circuit is usually used for wall receptacle outlets and room light fixtures.

Since most appliances are designed to operate with 120 V, such as the lighting and outlet recepticles, they are connected to the 120-V lines as in Circuits #1 & #2. Larger appliances requiring 240 V, are connected as in circuit #3.

To avoid trouble, insulation, grounding, fuses, and circuit breakers are used. Modern wiring codes require a third wire for a separate ground.

Because of the dangers of electricity, house wiring is carefully regulated by a code drawn by local ordinances and by the National Electrical Code (NEC).

Electrical outlets provide a means of connecting various devices which require electricity. There are many different types of outlets around the world, with varying voltage and electric current properties. Some are shown here.

As of the 2011 NEC, most new and replacement receptacles must be tamper-proof. This requirement is designed to protect small children from injury by preventing the insertion of objects, other than electrical plugs, into the receptacle contacts. Some exceptions to this requirement include wall receptacles that are more than 62 inches from floor level and large appliance receptacles located out of reach.

New wall receptacles will have two types of contacts: terminal screws on the sides, and holes in the back. The screws may be designed to secure a hooked wire to the device when driven home, or they may be used to tighten a clamp around the end of a straight wire.

The holes in the back of the device are used for inserting a straight wire into an internal clamp. The holes will be labeled to indicate what wire size they can accept.

Receptacles are available for 15 and 20 amp ratings. In older homes, the devices and wiring may be outdated and you will find receptacles that are ungrounded or even ungrounded and non-polarized.

This is a standard 15 and 20 amp, 120 volt wall receptacle outlet wiring diagrams. This is a polarized device. The long slot on the left is the neutral contact and the short slot on the right is the hot contact. A grounded contact at the bottom, center is crescent shaped. The hot screws are usually a brass colour. Neutral screws are usually silver in colour and ground screws are usually green.

The 15 amp, 120 V duplex receptacle outlet can typically be found in livingroom and bedroom wall outlets. One of these may be controlled with a switch and/or wired to other outlets in the circuit. For a 15 amp receptacle like this, 14/2 cable with ground should be used to feed the circuit.

A 20 amp, 120 V duplex receptacle outlet like this should be installed in a circuit using 12 awg cable and a 20 amp circuit breaker. These receptacles are usually found in kitchen wall outlets where two branch circuits are needed to serve small appliances and a refrigerator separately.

When using this device for heavy appliances like washing machines and microwaves, it should be connected to a dedicated 20 amp/120 V circuit breaker. Some electrical codes require circuits to be protected from Arc faults. This can be accomplished with the use of AFI breakers.

An AFI or Arc-Fault Interrupter, is a circuit breaker that breaks the circuit when it detects an electric arc that is a signature of loose connections in home wiring. Loose connections, which can develop over time, and can sometimes become hot enough to ignite house fires.

A residual-current device (RCD), residual-current circuit breaker (RCCB) or ground fault circuit interrupter (GFCI) sometimes simply refered to as a GFI, is an electrical safety device that quickly breaks an electrical circuit with leakage current to ground. It is to protect equipment and reduce the risk of serious harm from an ongoing electric shock.

These electrical wiring devices are designed to quickly and automatically isolate a circuit when it detects that the electric current is unbalanced between the supply and return conductors of a circuit.

They are designed to disconnect the conducting wires ("trip") quickly enough to potentially prevent serious injury to humans, and to prevent damage to electrical devices.

RCDs are testable and resettable devices. A test button safely creates a small leakage condition, and another button resets the conductors after a fault condition has been cleared.

This leakage can be detected either at the receptacle itself (self-contained GFI protection) or back at the power panel with a special breaker that will protect the whole circuit (circuit breaker GFI protection). The above drawing shows how both of these receptacles are connected.

This is the first entry for

Low Voltage Residential Wiring…more to follow

Blog #5 - Electrical Grounding

Grounding is a principle of electricity that sometimes puzzles homeowners. To understand its importance to a home wiring system, it is important to know something about the nature of electrical energy flow.

What Is Electrical Grounding?

Grounding offers excess electricity the most effective and safest route from an appliance back to the ground by way of an electrical panel. Electrical grounding is a backup pathway, that is generally only used if there is a fault in the wiring system.

Electrical service to North American homes began in the late 1890’s, and blossomed from 1920 to 1935, by which time, 70 percent of homes were connected to the electrical utility grid.

In the following 200 years, the methods for installing wiring in those homes has seen several important innovations, aimed at improving the safety of electrical systems.

Between eighteen 90 and 1910, a wiring system known as knob-and-tube, was the principal system of installation. It was quite a dependable system for the time, and a surprising number of homes still have knob-and-tube wiring functioning, where it is often found alongside more modern updates. In knob-and-tube wiring, individually conducting wires protected by a rubberized cloth fabric, are installed in stud and joist cavities, held in place by porcelain knob insulators, attached to the sides of framing members, and protected by porcelain tube insulators where the wires run through, the framing members.

In this wiring system, hot wires, and neutral wires, were run separately for safety. The system also allowed long circuit runs to be constructed by splicing together lengths of wire. To do this, the insulation was stripped back, a new wire was wrapped around the exposed bare wire, and the splice was soldered together then taped to cover the splice.

The downfall was the wire was exposed and there was no ground wire used. Where knob-and-tube wiring is still functioning, it is living on borrowed time, since the rubberized cloth insulation used on the wires has an expected lifespan of about 25 years, before it begins to crack and break down.

Electrical systems containing functioning knob-and-tube wiring are in critical need of an upgrade. But just because you see knob-and-tubes in some wall or floor cavities, doesn't necessarily mean you are in danger.

It was common practice to simply leave old wiring in place, but not energized, and functionally replaced when a home was rewired.

It's possible that the porcelain insulators and wires you see are merely antique remnants of earlier wiring installation.

In the 1920s to 1940s, electrical installations took a turn to a more protective wiring scheme, flexible armored cable or Flex, also known as Greenfield, was a welcomed addition to home wiring because the flexible metal jacket helped to protect the wires from damage, and also offered a metal pathway that could ground the system, when properly installed.

Although it was an improvement, this wiring method had its troubles. Although the individual wire conductors are protected, the flexible outer metal jacket serves as a proper ground only when the metal pathway is complete, all the way to the service entrance and grounding rod. There is still no separate ground wire in these installations.

Nonmetallic Sheathed Cable

In the 1930s, a quicker installation method was developed. Nonmetallic-sheathed cable was born, which incorporated a rubberized fabric coating sheath, much like knob and tube wiring, but here the hot and neutral wire were run together in this one sheathing. It also had its drawbacks due to the lack of a ground wire, but its development would eventually lead to major innovations.

Early sheathed cable, however, also has an expected lifespan of about 25 years, and where it is still in use, such installations need to be upgraded.

The Age of Metal Conduit

The newest addition to wiring was NMD, introduced in around 1965. This form of NMD cable was an update to older NM cable and incorporated the use of a bare copper grounding wire along with the insulated hot and neutral wires, contained within the sheathing. Instead of rubberized sheathing, modern NMD cable uses a very tough and durable vinyl sheathing. This update made the cable inexpensive and very easy to install. It is a very flexible product and is used extensively in virtually every new home built.

Along with NMD cable for interior use, a related type of cable was also developed for underground use. Underground feeder wire, (UF), can be buried directly under the ground without the need for a protecting conduit. This type of wire has a hot, a neutral, and a ground wire embedded in a solid plastic vinyl sheath that protects it from moisture. This offers an inexpensive method for running power underground to outbuildings and yard lights.

Through most of the history of residential electrical service, the preferred metal used in the conducting wires has been copper, known as the best conductor of electrical current. In the mid nineteen 60’s, when copper prices were quite high, aluminum came into vogue, as a material for electrical wiring. Residential installations between 1965 and 1974, sometimes used wires that were solid aluminum, or aluminum covered with a thin layer of copper.

Aluminum or copper-coated aluminum wiring is perfectly safe, if connected to receptacles, switches, and other devices, rated for use with aluminum, but it can pose problems, when it's installed with devices intended for use with copper wiring only.

Because of these issues, aluminum or copper-clad aluminum is no longer used in residential applications. It is for this reason, if you have aluminum wiring, repairs are best made by a professional.

To prevent electrical danger, your home's electrical system includes a backup plan, a system of grounding wires that runs parallel to the hot and neutral wires. It provides an alternate pathway for electrical current to follow should there be a breakdown in the system of hot and neutral wires, that normally carry the current. If a wire connection becomes loose, for example, or a rodent gnaws through a wire, the grounding system channels the stray current back to ground by this alternate pathway, tripping the breaker, before it can cause a fire or shock.

The grounding pathway is generally formed by a system of bare copper wires, that connect to every device, and every metal electrical box in your home.

In standard sheathed NM cable, this bare copper wire is included along with the insulated conducting wires inside the cable. The bare copper grounding wires terminate, in a grounding bar in your main service panel, and that grounding bar is in turn connected to a grounding rod driven deep into the earth outside your home.

This grounding system provides a path of least resistance for electricity to follow back to ground, should a break in the wiring system allow electricity to "leak" out of the preferred system of black and white circuit wires.

In most home wiring systems, evidence of the grounding system can be seen at each outlet receptacle, where the third round slot in the face of the receptacle represents the grounding connection. When a grounded appliance plugs into such a receptacle, its round grounding prong is now directly connected to the system of bare copper grounding wires inside the house circuits.

Not all homes have this elaborate and complete grounding system formed by a network of bare copper wires. While such a grounding system is standard in homes with circuit breakers that are wired with sheathed NM cable, older wiring systems installed before 1965 may be grounded through metal conduit or metal cable, not bare copper grounding wires. And even older systems installed before 1940 may not have any form of grounding at all. Such is the case in knob-and-tube wiring, where there is no grounding path of any kind. Many older systems have already been updated, and it is a good idea to have it done if your wiring is of this older generation. One clue that your wiring is old is when the outlet receptacles have two slots rather than three. This indicates the outlets may not be grounded.

Blog #4 - High Voltage Electrical Safety

High-Voltage Electrical Safety

and

Electrical Power Training

This post was gathered in part from a post on the Health, Safety, Security and Environment World (https://hsseworld.com/high-voltage-electrical-safety/)

While electrical power training, working safely around high-voltage conductors will be a challenge for many trainees as it is for workers. High-voltage systems are generally associated with utility services and heavy industry, such as pulp mills, sawmills, and mining operations. With care and precise planning, you can operate equipment and tools safely around these potentially lethal power lines.

This post is designed for workers who must work close to high-voltage equipment and conductors. It explains why high-voltage systems are dangerous. It lists the minimum distances you must keep away from live power lines and explains what you should do if you can’t maintain these limits of approach. It also describes common problem areas and gives safe work practices for working close to overhead lines around construction sites and for operating equipment around power lines.

Identifying High-Voltage Overhead Conductors

Overhead high-voltage conductors are usually installed at the top of utility poles. If there is more than one conductor, they are usually placed side by side on a cross arm. If there is a transformer on the pole, the high-voltage conductors are mounted above it. These are general guidelines. Employers are responsible for accurately determining the voltage of all conductors on the pole or in the work area.

An H-frame configuration may be used to facilitate the installation of transformer bank platforms on older systems. They are most often seen in alleys. This illustration shows a common single-pole configuration.

Electrical Distribution System

Electricity is transmitted from generating stations and substations via high-voltage transmission lines at 60–500 kV (60,000–500,000 V). These lines are located on top of large towers or poles in transmission rights-of-way. The voltage is reduced at substations in urban areas and distributed by overhead or underground distribution lines. The high-voltage lines on utility poles on our streets are typically at 4–25 kV (4,000–25,000 V).

Why Energized High-Voltage Systems are Dangerous

Accidents involving high voltages can result in severe injuries and death. When an electric current passes through the body, it generates heat and can extensively damage internal tissues. In some cases, the entry and exit wounds are so severe that a foot or hand has to be amputated. The electric current can also stop the heart.

Electricity seeks all paths to the ground. That path might include a tree, mobile equipment, or the human body. If a part of the equipment you are operating contacts a live power line, then anything in contact with your equipment will also become energized. The earth itself could become energized for some distance around your unit. Similarly, the ground could become energized if a tree makes contact with a power line or if a broken power line falls to the ground.

When the electrical flow reaches the ground, it spreads out like ripples in a pool of water. The voltage is very high where electrical contact is made with the ground. Farther away from this point, the voltage gradually drops off. Wet ground will extend the distance and the danger.

The voltage at the contact point is approximately the same as the line voltage. With power lines up to and including 60 kV (60,000 V), the voltage drops to zero about 10 m (33 ft.) away from the contact point with the ground. With higher voltages, such as those carried by the lines along transmission rights-of-way, the voltage might not drop to zero until you are as far away as 32 m (105 ft.).

If anything touches a high-voltage power line or if a power line falls to the ground, electricity will flow to the ground, energizing the tree or equipment and anything in contact with it. The surrounding ground may be extremely hazardous. The voltage gradually decreases from the point of contact until it reaches zero. The safe distance shown here — 10 m (33 ft.) — is for line voltages up to and including 60 kV (60,000 V) Whenever there is a voltage difference between one point and another, a current will flow. It is this flow of electricity (the current) that can cause serious injury or death.

Step Potential

Step potential is the voltage difference between two places that are a step apart on energized ground. For example, if you are standing on energized ground, there could be a significant difference in voltage between where one foot and the other are placed, and an electric current could flow up one leg and down the other.

Step potential: If your feet are spread apart on energized ground, electricity can flow through your body from the area of higher voltage to the area of lower voltage. If your feet are close together and touching, you are fairly safe. Since there is almost no voltage difference between the places where your feet stand, there is little reason for electricity to seek a path through your body. If you find yourself on energized ground and need to move away, you can avoid electric shock or electrocution because of step potential by making sure there is no space between your feet. Shuffle your feet while moving out of the energized area. When shuffling, keep your feet touching at all times to maintain the same voltage in both feet. Similarly, rescue workers must not enter an area that might be energized. Anyone trying to reach an injured worker in an energized area would be exposed to the same danger of step potential. The power lines must be de-energized and grounded before rescue workers or first aid attendants approach.

If you must move on energized ground, shuffle while keeping your feet together and touching each other. Don’t take steps.

Touch Potential

Touch potential is another danger that comes from the difference in voltage. It occurs when you touch something that is energized while standing on lower-voltage ground. For example, if a tree or equipment is in contact with a power line, it will be energized to the same voltage as the power line; the surrounding ground will be energized to a lower voltage. If you touch the energized equipment or tree at the same time as you touch the ground with your feet, electricity will flow through your body from the higher voltage tree or equipment to the lower voltage ground.

Touch potential: Trees and equipment become energized when they contact a power line. Electricity can flow through anyone who touches the energized tree or equipment, often causing serious injury or death.

Safety in The Event of Power Line Contact

Power lines can be brought down in a number of situations, including storms, trees, ice, and motor vehicle accidents. Even if the power line does not come down, if it is in contact with a tree, vehicle, or mobile equipment, the ground will be energized and so will the tree, vehicle, or equipment.

Workers in a Vehicle or Mobile Equipment

If electrical contact is made, stay in the vehicle or mobile equipment if it is safe to do so.

You are relatively safe inside your vehicle as long as you don’t touch or step onto anything outside the vehicle that will provide a path for the current to flow to ground. Wait until the owner of the power system has verified that the power lines have been de-energized and grounded. In one incident, for example, the raised box of a dump truck hit a 60 kV (60,000 V) power line. The driver stayed in the truck and was not injured, although all 18 tires were damaged by the electrical current.

If the vehicle is not damaged and is not entangled with the power line, it is safe to drive slowly out of the energized area, at least 10 m (33 ft.) clear of the wires and any wet ground. Because of the danger of exploding tires, large mobile equipment with inflated rubber tires should be moved to an open space away from workers and other equipment. There is a danger of exploding tires for up to 24 hours.

If you must abandon your vehicle because of an emergency such as a fire, be aware that the ground below your machine may be energized and use extreme caution.

To make a safe escape, keep both feet together and hands by your sides, and make a short jump from your vehicle. The goal is to ensure that your entire body clears the vehicle and that you land on your feet without stumbling. Don’t allow any part of your body to touch the vehicle while you are touching the ground.

Don’t take steps away from the vehicle. It is safest to shuffle away without moving your feet more than a few centimeters (a couple of inches) at a time. Keeping your feet together will ensure that you don’t straddle two zones with different voltages.

Rescue Work Around Power Lines

The main role of rescue workers near downed power lines or energized equipment is to stop people from getting hurt. Here are some safe work practices:

Treat downed lines and anything in contact with a power line as Energized wires seldom leap about and give off sparks, so you have no way of knowing whether or not they are energized. Even if the line is not energized, automatic switching equipment may restore power to the line without warning.

Park, and park your vehicle well away from any downed lines when you arrive at the scene. At night, shine a flashlight through the window to make sure you are not parked anywhere near a downed power line.

Stop traffic and keep people well away. Workers on foot or in vehicles may not see lines that are lying on the ground. The ground surrounding a downed line will be energized. If a live wire comes in contact with a vehicle, or anything else, that object becomes energized. Secure the area and keep everyone back at least 10 m (33 ft.)…more if the voltage is over 60 kV (60,000 V).

Don’t let yourself become a victim. Regardless of how badly someone is injured, you cannot help if you are electrocuted. Never touch anything that is in contact with a downed power line, including injured or trapped victims, puddles, vehicles, or trees. Don’t use a dry stick or piece of rope or hose as they will not offer any protection. Don’t enter an area that might be energized.

Call the owner of the power system and 911 (or other local emergency numbers). A crew with proper training and equipment will arrive as soon as possible.

Accept confirmation that the system has been de-energized and is safe only from a representative of the power system who is on site.

 

Hazard Alert Example

A vehicle contacted a high-voltage power line. When a police officer arrived at the scene, the vehicle was still energized. The police officer walked toward the vehicle. The officer’s legs started tingling about 2 m (6 ft.) away from the vehicle. The officer was fortunate not to be seriously injured or electrocuted.

General Limits of Approach

The key to safety is to keep a safe distance from overhead and underground power lines. OSHA (Occupational Safety and Health Administration) Regulations lists the distances that workers must keep away from exposed energized conductors.

The table gives the general limits of approach. This is the minimum distance from overhead energized high-voltage lines that non-qualified workers and their materials, equipment, and machinery must maintain.

The limits of approach vary with the voltage. The tools and equipment that you hold or operate are an extension of your reach. You must ensure that you have enough room for movement with your tools without violating these limits.

The movement of equipment and tools must be carefully planned to avoid entering within the general limits of approach. Employers must accurately determine the voltage and minimum limits of approach. To do so, contact the owner of the power system. Employers must also ensure that:

  • Supervisors and workers know the location of all electrical power sources in the work area before starting work

  • Supervisors review the general limits of approach with all workers working near energized HV equipment or power lines

  • Supervisors hold pre-job safety meetings (tailgate meetings) and document the meetings

Supervisors and workers must maintain the minimum distance from electrical conductors at all times. The minimum distance is measured from the extreme outside dimension of mobile equipment, tools, or materials being handled. The outside dimension may be the tip of an extended equipment boom, a paint roller, or a long pipe that you are lifting. The electrical conductor may be a wire, a transformer, or any other energized component that conducts electricity. All workers need to know the safe limits of approach to electrical conductors and must not get any closer.

Working Inside the Limits of Approach

After first checking the work site, you may find that the minimum distance from the electrical conductor cannot be maintained. If inadvertent movement by a worker or equipment may result in either coming closer than these minimum distances, you must follow these steps before proceeding with work:

1. Call the owner of the power system and arrange for a worksite meeting to decide whether the energized electrical conductors can be:

• Displaced or rerouted, or

• De-energized (isolated and grounded), or

• Visually identified safe working area

2. Get assurance in writing from the owner of the power system indicating which of the three actions will be taken. No work can be done within the limits of approach until one of the conditions in step 1 has been met. It takes time to complete the process, so it’s important to plan.

3. Inform all workers near the power lines of this information and make sure they are trained in appropriate safe work procedures.

4. Designate a qualified safety watcher who can monitor equipment and material movement and give an instant “stop” signal to the equipment operator when the equipment or load is too close to the electrical conductor. Workers, equipment, tools, and loads must not contact the guarding under any circumstances.

Hazard Alert

A tower crane operator working from the top of a high-rise building was hoisting material to different floors. The operator had completed a lift and returned the bucket to the ground loading area. While the operator was re-positioning the bucket, the hoist cable slackened excessively and crossed over a 12 kV (12,000 V) power line, energizing the hoist cable. Fortunately, no one was injured in this near miss

Guarding is a visual warning only. The grounded guard wire (with flags) gives a warning of approach. The overhead line cover-ups, installed by the owner of the power system, have no insulated rating. Workers and equipment must not contact the guards or overhead line under any circumstances. Serious injuries or death can result if any part of a crane touches a power line.

Recertifying Equipment After Electrical Contact

When a machine contacts a power line, the passage of current through the machine can impair the strength of some of its parts. Any hoisting or aerial device that has contacted an energized conductor must be recertified by a professional engineer before it is returned to service. It is recommended that a licensed mechanic check other mobile equipment that has contacted a power line.


Construction Sites Near Power Lines

Each year workers in many places die or are seriously burned as a result of unsafe work practices around energized conductors. The following information is a reminder to operators of construction equipment and to construction and maintenance workers who must work near power lines:

• Most power lines are found overhead; however, some are buried just a short distance below the surface of the

• The normal operating range of your machine or equipment can often reach either the overhead or the underground power lines above or below

• Supervisors and operators of equipment can prevent electrical accidents through knowledge of electrical systems and safe work

Mobile Equipment Near Power Lines

Operators of mobile equipment such as cranes, hoists, and backhoes must take care that no part of the equipment makes contact with an overhead power line. If any part of the equipment contacts an overhead power line, remember that the operator is safer inside the machine than on the ground. If mobile equipment touches a power line, electricity can travel from the power line to a worker touching any part of the equipment, including a pendant control.

A worker was on the ground guiding a mobile crane onto a truck deck when the crane’s boom contacted a power line. The electrical current passed through the crane jib that the worker was holding and then passed through the worker to the ground. The worker was electrocuted.

In another accident, a pumper truck operator was lowering the truck’s boom after pouring concrete. He was standing away from the truck using the pendant control. The boom contacted the high-voltage line and power came through the pendant line to the operator. The operator was electrocuted.

If you operate mobile equipment near power lines, take the following precautions:

1. Keep your mobile equipment, work materials, and tools at a safe distance from power lines. This is your first line of defense when operating mobile equipment near overhead power lines.

2. If it is necessary to operate equipment closer than 6 m (20 ft.) to a power line, contact the owner of the power system to find out the voltage of the line. Then find the minimum distance away from the line you are allowed to work. If it is not possible to keep this distance, the owner of the power system may need to de-energize or reroute the circuit, or provide guarding. Don’t proceed until the owner of the power system has given written assurance defining proper

3. Don’t stand on the ground beside your machine to operate the remote controls for the equipment. If a power line contact occurs, current will flow through the machine to the ground. If your feet are on the ground and you touch the electrified machine, current will pass through your body to the ground. An electrical contact will also energize the ground around the machine for some distance, up to at least 10 m (33 ft.) — more if the lines carry voltages higher than 60 kV (60,000 V).

4. If you must operate controls from the ground, the remote control signal should be carried by radio or non-conductive cable such as fiber. If the fiber optic cable has armored with metal bands, it will be conductive. In addition, you should stand well clear when operating equipment with a remote control - depending on the voltage, at least 10 m (33 ft.) away from your machine and the power lines.

Traveling Under Power Lines

Know the height of your load and the height of the power lines you will be traveling under. Always make sure there is sufficient clearance for your load to travel safely under the power lines.

Hazard Alert

The height of all mobile equipment must be minimized before transporting near high voltage lines, for example the boom of a grapple yarder must been lowered for transport.

Pruning or Falling Trees Near Power Lines

Workers have been killed or injured when doing tree care work or falling trees near power lines. Before workers prune or fall trees close to a power line, a qualified person must inspect the worksite to identify any hazards, including situations where any part of a tree is within the general limits of approach or could fall within that distance. The owner of the power system must authorize the person doing the inspection and ensure that the person is qualified.

If tree pruning or falling will come within the general limits of approach, workers must be authorized by the owner of the power system to do the work. Normally the only worker authorized to do this work will be a qualified electrical worker, a certified utility arborist, or an apprentice utility arborist working under the direct supervision of a certified utility arborist or a qualified electrical worker.

Tree pruning or falling is not allowed within the general limits of approach unless both of the following are true:

1. A certified utility arborist or qualified electrical worker is present at the site and directing the work

2. At least one additional qualified person, trained in appropriate emergency rescue, is present

A Working Example

A tree trimmer was up in a tree trimming branches about 2.5 m (8 ft.) away from a power line. When he cut a tree branch, it fell onto the power line and the other end hung against the trunk of the tree. The worker received a fatal shock when he tried to free the branch from the tree.

Scaffolds and Other Equipment Near Power Lines

The limits of approach must be maintained for all scaffolds and equipment near power lines. For example, workers on scaffolds or window-washing platforms must not let any tools, such as pipes or rollers, come within the limits of approach. Scaffolds must be positioned and secured in a manner to prevent them from coming into contact with adjacent power lines.

Farm equipment can cause accidents when it contacts power lines. Farm workers have been electrocuted when metal irrigation pipes have been lifted up, touching overhead power lines. Where practicable, store metal irrigation pipes at least 30 m (100 ft.) away from overhead power lines.

A tool is an extension of your reach and must not come within the limits of approach. A construction worker was erecting tubular scaffolding 3 m (10 ft.) from an energized 25 kV (25,000 V) conductor. The worker was handling a long section of bracing, which accidentally contacted the power line. The worker was electrocuted.

A worker was excavating a trench beside a utility pole. The pole was undermined when too much soil was removed next to the pole. The pole fell over, causing high-voltage lines to fall near the worker. Fortunately, the worker was not injured.

Utility poles

Don’t work close to utility poles if the work could cause a pole to become unstable or if you can’t maintain the limits of approach. If any poles are unstable, ask the owner of the power system to support or remove them. Workers must not climb poles supporting power lines unless they are qualified and authorized by the owner of the utility.

Underground utilities

Low-voltage and high-voltage underground wiring is used for supplying power to schools, commercial buildings, homes, and numerous other sites. Drilling, excavating, or probing can be dangerous near buried electrical lines. Check with the owner of the power system for the existence and location of underground lines before you start digging.

Workers have died because their shovel blade penetrated a live high- voltage electrical cable. A treated-wood plank buried on top of the cable may be the only protection for the cable. Modern installations often have a bright yellow plastic ribbon buried below the surface to warn that a cable lies beneath it. “Danger — High Voltage” signs warn that high-voltage equipment is enclosed inside and buried underground. Don’t take chances — contact the owner of the power system before you start digging. You must accurately identify the location of underground utilities before you dig. Besides electricity, there are other kinds of underground utilities, including telephone, gas, cable, water, and pipeline services.

Find Out the Locations of any Underground Cables

Before You Begin Work

The following activities are potentially hazardous because workers may contact buried power lines:

• Driving ground rods or any other long metal objects into the ground

• Digging holes for fence posts

• Digging near “Danger — High Voltage” signs

• Trenching

Locate Cables First

A worker was breaking concrete when his jackhammer broke through a conduit. The tool contacted an energized 15 kV (15,000 V) underground cable. The worker was electrocuted.

Conclusion

3 Keys of Electrical Safety

1. Look up and down.

All workers who operate machinery or equipment that could come in contact with power lines should look up and check for overhead power lines before beginning work or identify underground power lines in the vicinity. Plan your work to prevent electrical contact.

2. Keep back — Know your limits.

When operating machinery or equipment in close proximity to power lines, always maintain the limits of approach: 3–6 m (10–20 ft.), depending on the voltage. Use a spotter to make sure you keep equipment away from power lines.

Where any portion of a machine or equipment may come closer than the minimum distance, contact the power system owner to provide some form of protection.

On the ground stay at least 10 m (33 ft.) away from operating equipment because if it contacts an energized line the electricity will go to ground. The operator should be on the vehicle with everyone else clear of the vehicle when the boom is in motion. If you must approach, ensure the equipment is not operating.

3. Stay back, and call for help.

Stay back at least 10 m (33 ft.) from a fallen power line, exposed underground power line, or any object in contact with the line. If the machinery you are operating contacts an energized line, move it away from the line to break contact. If you can’t do this, stay put in the machine until help arrives.

If it’s a life-threatening situation such as a fire, jump clear of the machine, keeping your feet together. Never contact the machine and the ground at the same time. Once clear of the machine, shuffle away, never allowing the heel of one foot to move beyond the toe of the other. Keep shuffling until you are at least 10 m (33 ft.) away from the machine; this is the safe distance for voltages up to and including 60kV (60,000 V).

Depending on the voltage, you may need to get as much as 32 m (105 ft.) away from the machine.

Always call your local emergency services when someone is injured in an electrical accident. Don’t attempt a rescue until directed by qualified personnel. If you touch an injured person who is still in contact with an electrical source, you could be seriously injured or killed. Keep everyone back at least 10 m (33 ft.), and have someone call for help immediately.

Blog #3 - PPE (Personal Protective Equipment)

Electrical Safety

and

PPE (Personal Protective Equipment)

Introduction

Electrical safety is one of the most important aspects of electrical work. During my career in the electrical power utility industry, this fact was indelibly imprinted on my mind, which not only helped me on the job, but off the job as well. I do believe that repetition was the key. So, on this site and in these blogs, you’ll find a return to this subject matter often. Because this site, my courses and this blog, reaches thousands of students internationally, I’m going start off with my first safety blog with seemingly a simplistic approach, but after I set the foundation, I will move on to more sophisticated safety topics in later posts.

Electrical professionals must follow all local, state, and federal regulations when they are working with electricity. There are several items of PPE (Personal Protective Equipment) that electrical professionals must wear in order to protect themselves and others.

There are several items of PPE Personal Protective Equipment that electrical professionals must wear in order to protect themselves and others.

PPE Personal Protective Equipment is required by law, and is essential to the safety of people working on electrical equipment. The following types of PPE must be worn at all times:

  • Rubber-soled shoes or boots

  • Leather work gloves (insulated)

  • Protective clothing covering the arms, legs, and torso (this may or may not include fire retardant material)

Electrical professionals must also wear their hard hat in addition to these items.

A hard hat is a very important piece of protective equipment

Gloves protect the hands from the elements, cuts, scrapes, and in some cases serious burns


Boots help to protect your feet from falling objects and also from electrocution.

Boots can help to protect your feet from falling objects and also from electrocution.

  • Electrical safety is important.

  • Boots should be made of leather or rubber, insulated, and high enough to protect your ankles. They should also be non-conductive (electrical resistive).

Safety glasses can protect the eyes from flying debris.

Conclusion

The electrical safety rules are simple and easy to understand, but not always easy to follow. Electrical professionals should remember that electricity is a dangerous thing and must be treated with respect at all times.

Blog #2 - 5 Electrical Hazards

5 Electrical Hazards to Watch Out for When Electrical Power Systems Training

1) Wearing Personal Protective Equipment

PPE (Personal Protective Equipment) is essential when Electrical Power Systems Training in an electrical environment. Electrocution, electric shock, burns, and falls are all common injuries that a worker or student must be hyper-aware of avoiding. During even basic electrical training online, you’ll learn that the first preventative measure that you can take is equipping yourself with the appropriate Personal Protective Equipment.

There are many different types of PPE you can protect yourself with, depending on the scope of the job. Insulated gloves, matting, and ladders can provide a protective layer eliminating a pathway for electricity to travel through the body. Face shields, non-metal helmets, and flame/flash retardant clothing can also add extra protection. Additionally, you should always inspect your PPE before use, and be sure to safely store it after completing a job. Ensure that you’re always wearing proper PPE.


2) Beware of Improper Grounding and Unwanted Voltage.

Grounding is the method of connecting an isolated conductor to ground, preventing unwanted transmission and voltage. When an electrical system is not appropriately grounded it can create a voltage that cannot be eliminated safely, as the exposed parts of a system can become energized and cause electrocution. This can include the metal parts of motors, appliances, or electronics that are plugged in.

To prevent electrical hazards, equipment must always be properly grounded. Using a Ground Fault Circuit Interrupter (GFCI) is a recommended safety measure that can safeguard you from improper grounding when working with electrical systems. If a ground fault is detected in a circuit protected by a GFCI, it automatically stops the current, protecting you from electrocution.


During your training, you’ll learn about using the LOTO method to control hazardous energy and prevent the accidental use of equipment while it is unsafe, being inspected, or being worked on.

Lockout and Tagout ensures that equipment is appropriately shut off and unable to be restarted prior to the completion of any work being done. When the power sources are off, they are locked with a tag attached identifying the reason the LOTO is there. The worker that places the LOTO is the only one with the key, ensuring that it is not accidentally started by anyone else.


4) Working in a Wet Environment Increases the Chance of Electrocution


5) Overloaded Power Strips and Outlets Are a Common Hazard

One of the most common electrical hazards in many homes and businesses are overloaded power strips and outlets. Outlets are designed for a limited amount of electricity output. Plugging in an excess of devices can overload a power strip, increasing the chances of an electrical fire. Choosing power strips with surge protection will help to reduce the risk of fire, as the breaker stops the current if it gets overloaded. However, when working with heavy electric equipment, you cannot rely on common surge protectors and power strips. Instead, a safer alternative is a three-way extension with GFCI for added protection.

With an extensive hands-on learning experience, as well proper safety techniques and leading practices, you will be fully prepared to identify and avoid common electrical hazards throughout your future career.